Table 1:Typical Flow Rates
|
GPM(ma/hr)Required to Actuate Switch
|
|||||||||||
|
Pipe Size(in.)
|
1
|
1-1/4
|
1-1/2
|
2
|
2-1/2
|
3
|
4*
|
5*
|
6*
|
8*
|
|
| Minimum Adjustment |
Flow Increase R to Y Closes** |
4.2 (1.0) |
5.8 (1.3) |
7.5 (1.7) |
13.7 (3.1) |
18.0 (4.1) |
27.5 (6.2) |
65.0 (14.8) 37.0+ (8.4) |
125.0 (28.4) 57.0+ (12.9) |
190.0 (43.1) 74.0+ (16.8) |
375.0 |
| Flow Increase R to B Closes** |
2.5 (0.6) |
3.7 (0.8) |
5.0 (1.1) |
9.5 (2.2) |
12.5 (2.8) |
19.0 (4.3) |
50.0 (11.4) 27.0+ (6.1) |
101.0 (22.9) 41.0+ (9.3) |
158.0 (35.9) 54.0+ (12.3) |
320.0 (72.7) 170.0+ (38.6) |
|
| Maximum Adjustment |
Flow Increase R to Y Closes** |
8.8 (2.0) |
13.3 (3.0) |
19.2 (4.4) |
29.0 (6.6) |
34.5 (7.8) |
53.0 (12.0) |
128.0 (29.1) 81.0+ (18.4) |
245.0 (55.6) 118.0+ (26.8) |
375.0 (85.2) 144.0+ (32.7) |
760.0 (172.6) 415.0+ (94.2) |
| Flow Increase R to B Closes** |
8.5 (1.9) |
12.5 (2.8) |
18.0 (4.1) |
27.0 (6.1) |
32.0 (7.3) |
50.0 (11.4) |
122.0 (27.7) 76.0+ (17.3) |
235.0 (53.4)) 111.0+ (25.2) |
360.0 (81.8) 135.0+ (30.7) |
730.0 (165.8) 400.0+ (90.8) |
|
|
Product
|
F61KB Flow Switch | |||
|
Maximum Liquid Pressure
|
150psig(1034kPa) | |||
|
Minimum Liquid Temperature
|
32ºF(0ºC) | |||
|
Maximum Liquid Temperature
|
250ºF(120ºC) | |||
|
Electrical Ratings
|
120VAC | 208VAC | 240VAC | 277VAC |
|
Horsepower
|
1 | 1 | 1 | - |
|
Full Load Amperes
|
16.0 | 8.8 | 8.0 | - |
|
Locked Rotor Amperes
|
96.0 | 52.8 | 48.0 | - |
|
Non-inductive Amperes
|
16.0 | 16.0 | 16.0 | 16.0 |
|
Pllot Duty
|
125VA at 24/277/VAC
|
|||
|
Wiring Connection
|
Screw Type Terminals
|
|||
|
Pipe Connector
|
1 in. 11-1/2 NPT Threads
|
|||
Conduit Connection One 7/8 in. (22mm)Hole For1/2in.Conduit with 1-3/32 in.(28mm)knockout Ring for 3/4 in. conduit.
F61KB Liquid Flow Switch
The F61 Liquid Flow Switches are single-Pole, Double-Throw (SPDT) flow switches that are used in liquid lines carrying water, ethylene glycol, or otherliquids not classified as hazardous.they can be wired to energize one device and de-energize another device powered from the same source when liquid flow either exceeds or drops below the set flow either exceeds or drops below the set flow rate.
Note: The F61 Flow Switch Cannot be used where the liquid in the pipes will drip below the liquid’s freezing point, causing an internal freeze-up.
IMPORTANT:F61 Flow Switches are designed for use ONLY as operating controls. Where an operating Control failure would result in personal injury and/or loss of property, it is the responsibility of the installer to add devices (safety, limit controls)or systems(alarm, supervisory systems)that protect against or warn of control failure.
Bookmark this page